EX KNOWLEDGE / 01 — FUNDAMENTALS

Introduction to Hazardous Areas

A hazardous area is a location where an explosive atmosphere may occur in quantities that require special precautions for the design, installation and use of electrical equipment. Understanding why an area is hazardous is the first step toward selecting the correct explosion-protected equipment.

THE BASIC PRINCIPLE

How can an explosion occur?

An explosion can occur when a flammable substance, oxygen and an effective ignition source are present together in suitable conditions.

Fuel — flammable substance

A flammable gas, vapour, mist or combustible dust can form an explosive atmosphere when mixed with air in suitable concentrations.

RISK CONTROL

How is the risk managed?

Explosion protection is not based on one device or one marking. It combines area classification, equipment selection, correct installation and inspection.

01 — IdentifyIdentify flammable substances, release sources, ventilation and operating conditions.
02 — ClassifyDetermine the hazardous area zone based on the likelihood and duration of an explosive atmosphere.
03 — ProtectSelect certified equipment and ensure it is installed, inspected and maintained correctly.
Important distinction

Hazardous area classification describes the area. The Ex marking and certificate describe the equipment protection and its permitted conditions of use. They are related, but they are not interchangeable.

INTERACTIVE AREA CLASSIFICATION

Gas, vapour or dust: which zone applies?

Choose the type of explosive atmosphere to explore the corresponding zone system. Select any zone to view its meaning.

Zone 0 — Gas / Vapour / Mist

An explosive gas atmosphere is present continuously, for long periods or frequently. Equipment selection requires the appropriate protection level for this zone.

Typical EPL: Ga
Zone numbers are different for gas and dust

Gas / vapour zones are 0, 1 and 2. Combustible dust zones are 20, 21 and 22. Do not use the gas-zone definitions or equipment selection assumptions for dust areas.

NEXT TOPIC

Ex Classification Explorer

Explore equipment marking, groups, categories, temperature classes and EPL.

Explore Classification
WIACS Technical Learning

Understanding Ex Equipment Marking

Learn how to read and interpret explosion protection markings. Explore the meaning of each marking element, from protection concepts and equipment groups to temperature classes and hazardous area zones.

Explore an Ex Equipment Marking

Select a protection concept and application to explore an illustrative equipment marking. Click on any part of the marking to understand what it means.

Illustrative Ex Marking
/ / / / /
Select any marking element above to see its explanation.

Equipment Group – II

Group II equipment is intended for use in places with explosive gas atmospheres, other than mines susceptible to firedamp.

Complete Marking Breakdown

Understand the main elements commonly found in explosion-protected equipment markings.

01

Equipment Group

Identifies the group of hazardous environments for which the equipment is intended.

02

Equipment Category

Indicates the equipment protection level and intended application under ATEX.

03

Protection Concept

Identifies the explosion protection method used in the equipment design.

04

Gas Group

Indicates the gas or vapour subgroup for which the equipment is suitable.

05

Temperature Class

Specifies the maximum equipment surface temperature under the stated conditions.

06

Equipment Protection Level

Indicates the level of protection provided in relation to the likelihood of an explosive atmosphere.

!

Technical Note: The markings shown in this interactive example are illustrative only. Actual equipment markings, certification details and permitted applications must always be verified against the product certificate, applicable standards and project requirements. Equipment selection should consider the hazardous area classification, gas or dust group, temperature requirements and installation conditions.

Explore Explosion Protection Methods

Learn more about the different protection concepts used in hazardous area equipment.

Explore Protection Methods →
EX KNOWLEDGE / INTERACTIVE TECHNICAL TOOL

Ex Equipment Selection Guide

Build a preliminary equipment requirement profile based on the equipment type, hazardous area classification, application-specific requirements and certification expectations.

5-Step Selection Process Equipment-Specific Requirements ATEX / IECEx Considerations
Step 1 — Select Equipment 01 / 05
1 Equipment
2 Area
3 Requirements
4 Certification
5 Review
STEP 01 / EQUIPMENT TYPE

What type of equipment are you selecting?

Choose the equipment category to load its relevant technical requirements.

Please select an equipment type to continue.
STEP 02 / HAZARDOUS AREA

Identify the hazardous atmosphere

Select the atmosphere type and the zone established by the area classification documentation.

An explosive gas atmosphere is likely to occur occasionally in normal operation.
Gb
This is a typical zone-to-EPL association, not an equipment approval.
Understanding the zone

Zone 1: An explosive gas atmosphere is likely to occur occasionally in normal operation.

Classification must come from the project

This tool does not determine or classify the hazardous area. Use the approved area classification dossier and confirm the applicable zone with the responsible engineering team.

Please confirm the hazardous area information.
STEP 03 / EQUIPMENT-SPECIFIC REQUIREMENTS

Define the equipment requirements

Enter the application and technical parameters relevant to your selected equipment.

Why these details matter

Equipment selection depends on more than the hazardous zone. Electrical ratings, construction, installation method, environmental conditions and certified product limitations must also be considered.

Do not assume a standard configuration

Where a value is not yet known, use “To be confirmed”. Do not treat an assumed value as an approved project requirement.

Please complete the required information or select "To be confirmed".
STEP 04 / CERTIFICATION & PROTECTION

Define the certification expectations

Record the project's certification requirements and any specified protection concept. This step does not automatically approve a protection method.

Confirm the destination market and project specification.
A project may specify a higher EPL than the typical minimum association.
Only select a concept if it is specified or established by the design.
Confirm actual site minimum and maximum ambient temperatures.
Typical minimum EPL reference

For the selected zone, the typical minimum EPL association is Gb. This is a reference only and does not replace equipment assessment.

Certification is product-specific

Verify the certificate number, exact model, ratings, marking, certificate schedule, special conditions of use and any applicable national requirements. A certificate logo or general product-family statement is not sufficient evidence by itself.

Please review the certification and protection requirements.
STEP 05 / SELECTION REVIEW

Your preliminary equipment requirement profile

Review the information entered and the technical points that must be verified before selecting a product.

PRELIMINARY SELECTION PROFILE

Lighting Fixture

Preliminary technical profile — not an approval
Equipment-specific technical summary
Technical verification checklist
Important — Educational guidance only

This tool generates a preliminary requirement profile. It does not certify equipment suitability or replace the hazardous area classification dossier, applicable standards, manufacturer documentation, certificate review or competent engineering assessment. Final selection must consider the complete equipment marking, certificate schedule, special conditions of use, installation requirements and actual site conditions.

WIACS Ex Knowledge — This interactive guide supports preliminary technical requirement collection. Always verify complete equipment certification, conditions of use and installation requirements.

WIACS EX KNOWLEDGE

ATEX vs IECEx

Understanding the difference between the European ATEX legal framework and the international IECEx certification system — and knowing what each one means for hazardous-area equipment.

European Regulatory Framework International Certification System Explosion Protection
01 / THE BASICS

Two Systems. Different Purposes.

Both address explosion protection, but they are not interchangeable.

ATEX

ATEX

European Union Legal Framework

ATEX refers to European legislation governing equipment and protective systems intended for use in potentially explosive atmospheres. The equipment directive is 2014/34/EU.

NatureEU legislation
ScopeProducts placed on the EU market within its scope
MarkingCE marking, Ex marking and equipment group/category markings, as applicable
DocumentsEU Declaration of Conformity and relevant conformity assessment documentation
IECEx

IECEx

International Certification System

IECEx is an international conformity assessment system based on relevant IEC standards. Its Certified Equipment Scheme provides independent assessment and certification of Ex equipment.

NatureInternational certification system
ScopeInternational system; national acceptance requirements vary
MarkingEx protection concept and equipment protection level (EPL), as applicable
DocumentsIECEx Certificate of Conformity (CoC), with supporting ExTR and QAR
02 / INTERACTIVE COMPARISON

Compare ATEX and IECEx

Select a view to explore the main differences.

Comparison
ATEX
IECEx
Nature of the system
European legal framework.
International conformity assessment and certification system.
Geographical application
EU market, subject to the directive's scope and applicable rules.
International system; acceptance depends on national regulations and project requirements.
Technical standards
Harmonised European standards can provide presumption of conformity with relevant essential requirements.
Based on applicable IEC standards, including relevant IEC 60079 standards.
Assessment bodies
Notified Bodies are involved where required by the applicable conformity assessment procedure.
Approved IECEx Certification Bodies (ExCBs) issue IECEx certificates, supported by the scheme's assessment process.
Equipment marking
CE marking and specific Ex marking, including equipment group and category where applicable.
Ex marking with protection concept and EPL; ATEX category is not an IECEx category.
Key documents
EU Declaration of Conformity; relevant EU-type examination certificate where applicable.
IECEx Certificate of Conformity (CoC), Ex Test Report (ExTR) and Quality Assessment Report (QAR).
Market access
Compliance is required for products within the directive's scope placed on the EU market.
Does not automatically grant market access in every country; local acceptance must be checked.
!
Important: IECEx certification does not automatically replace ATEX conformity requirements for equipment placed on the EU market. Likewise, ATEX conformity does not automatically mean that the product holds an IECEx Certificate of Conformity.
03 / CERTIFICATION PROCESS

How Does Certification Work?

The assessment routes differ, even though both involve technical evaluation and conformity evidence.

ATEX — Typical conformity route

01
Identify the applicable requirementsDetermine the equipment group, category, intended use and applicable essential health and safety requirements.
02
Conformity assessmentFollow the conformity assessment procedure applicable to the equipment group, category and product type. A Notified Body participates where that procedure requires it; the manufacturer remains responsible for the applicable obligations.
03
Technical documentationCompile the technical documentation, risk assessment and supporting evidence required by the applicable procedure. The documentation must support the manufacturer’s declaration of conformity.
04
EU Declaration of Conformity and CE markingThe manufacturer completes the applicable obligations and affixes the required markings.

IECEx — Certified Equipment Scheme

01
Product testing and assessmentAn IECEx accepted Ex Testing Laboratory (ExTL) performs the required testing and prepares the technical assessment. An IECEx Certification Body (ExCB) is responsible for the certification decision.
02
Ex Test Report (ExTR)The ExTR records the test results and technical assessment against the applicable IEC standards. It is prepared within the IECEx scheme by an accepted ExTL.
03
Quality Assessment Report (QAR)The manufacturer’s quality management system and relevant production location are assessed under the IECEx scheme. Continued surveillance is required to maintain certification.
04
IECEx Certificate of ConformityThe IECEx ExCB reviews the required assessment documentation, including the ExTR and QAR, and issues the CoC when the scheme requirements are met.
i
Technical note: ATEX conformity assessment routes vary according to equipment group, category and product type; Notified Body involvement is required only where the applicable procedure specifies it. Under the IECEx Certified Equipment Scheme, the ExTL performs testing and prepares the ExTR, while the ExCB makes the certification decision. The QAR addresses the manufacturer’s quality system and production controls.
04 / EQUIPMENT MARKING

Understanding the Marking Difference

The marking systems communicate related protection information, but their structures are not identical.

ATEX Equipment Marking

Illustrative example of an ATEX equipment marking:

II 2G Ex db IIC T4 Gb
II — Equipment Group II
2G — Category 2, Gas atmosphere
Ex db — Flameproof protection
IIC — Gas subgroup
T4 — Temperature class
Gb — Equipment Protection Level

IECEx Equipment Marking

Illustrative example of an IECEx-style Ex marking:

Ex db IIC T4 Gb
Ex db — Flameproof protection
IIC — Gas subgroup
T4 — Temperature class
Gb — Equipment Protection Level

IECEx marking does not use the ATEX equipment category designation such as 2G.
!
Do not assess equipment from the marking alone. Always verify the actual certificate, scope, special conditions of use, ambient temperature range, standards edition and product identification. The examples above are educational illustrations, not certificates for actual products.
05 / PRACTICAL APPLICATION

Which Certification Do You Need?

Choose the project situation to see what should be checked.

Project Requirement Checker

Select the scenario that best describes your project.

Recommended compliance check

    06 / KNOWLEDGE CHECK

    Test Your Understanding

    One practical question to check the key difference.

    A manufacturer has an IECEx Certificate of Conformity for an Ex luminaire. Can this certificate alone be considered sufficient for placing the product on the EU market under ATEX?

    INTERACTIVE LEARNING

    Ex Classification Explorer

    Explore the different elements of explosion-protected equipment marking. Select any classification to understand its meaning and relationship with other Ex requirements.

    EXPLORE THE SYSTEM

    Interactive Classification Map

    Select any marking element or classification card to explore its technical meaning.

    07 CLASSIFICATION ELEMENTS
    UNDERSTANDING AN EX MARKING
    Ex
    Select any highlighted element to jump to its explanation below. Example: II 2G Ex db IIC T4 Gb.
    SELECTED CLASSIFICATION

    Equipment Group

    01
    Group II

    CLASSIFICATION / TYPES
    RELATION TO OTHER ELEMENTS

    IMPORTANT TECHNICAL NOTE

    QUICK REFERENCE

    Hazardous Area Zone Classification

    Understand the difference between gas and dust hazardous area zones.

    Gas Atmospheres

    Dust Atmospheres

    Gas AtmospheresZone 0 → Zone 1 → Zone 2
    Dust AtmospheresZone 20 → Zone 21 → Zone 22
    Selection reminder: Zone classification describes the hazardous location, while equipment marking describes the certified protection characteristics of the product. Always verify both against the project documentation.
    ENGINEERING & EQUIPMENT SELECTION

    Protection Concepts – Technical Selection Guide

    Understand the technical differences between explosion protection concepts and the key factors to consider when selecting Ex equipment for industrial applications.

    Compare Protection Concepts

    Select a comparison to explore the differences in protection principles, design requirements and typical applications.

    EX
    GUIDE

    Ex db vs Ex eb

    Two different approaches to preventing ignition in hazardous areas.

    Ex db

    Flameproof Enclosure

    DESIGN APPROACH

    SELECTION CONSIDERATION

    VS
    Ex eb

    Increased Safety

    DESIGN APPROACH

    SELECTION CONSIDERATION

    i
    ENGINEERING DIFFERENCE

    Where Are These Concepts Commonly Used?

    Examples of equipment and protection concepts frequently encountered in industrial hazardous-area projects.

    01

    Electric Motors

    Motor protection depends on the motor design, starting conditions, operating characteristics and certified construction.

    Ex dbEx ebEx ec
    02

    Lighting Fixtures

    Lighting selection involves the protection concept, thermal performance, installation arrangement and area classification.

    Ex dbEx ebEx tb
    03

    Junction & Terminal Boxes

    Enclosure design, terminal arrangement, wiring requirements and the certified configuration are key selection factors.

    Ex ebEx db
    04

    Instrumentation

    Field instruments and signal circuits require assessment of electrical parameters, loop design and associated apparatus.

    Ex iaEx ibEx db
    05

    Control Cabinets

    Large or complex electrical assemblies may require a protection solution based on enclosure design and operating conditions.

    Ex pEx db
    06

    Dust Hazardous Areas

    Equipment for combustible dust environments requires assessment of dust ingress, surface temperature and enclosure protection.

    Ex tbEx tcEx ta

    These are representative application examples, not fixed equipment-to-concept assignments. The actual protection method must be verified against the complete equipment marking and certificate.

    What Should Be Checked Before Selecting Ex Equipment?

    Protection concept is only one part of the equipment selection process. Review the following factors before approving a product for a project.

    01
    Hazardous Area Classification

    Confirm the classified zone, gas or dust atmosphere, and the required equipment protection level.

    02
    Gas or Dust Group

    Verify the required gas subgroup (IIA, IIB, IIC) or dust subgroup (IIIA, IIIB, IIIC), as applicable.

    03
    Temperature Requirements

    Check the gas temperature class or the maximum permitted equipment surface temperature for dust applications.

    04
    Equipment Protection Level

    Verify that the EPL and ATEX category, where applicable, meet the project requirements.

    05
    Ambient Conditions

    Check ambient temperature range, ingress protection, corrosion exposure and environmental conditions.

    06
    Certificate & Configuration

    Review the certificate schedule, model, accessories, cable entries and special conditions of use.

    07
    Installation Requirements

    Confirm cable glands, wiring methods, earthing, mounting arrangement and applicable installation standards.

    08
    Operating Conditions

    Consider duty cycle, starting current, thermal loading, maintenance access and process conditions.

    Common Ex Equipment Selection Mistakes

    Issues that can lead to incorrect equipment selection or non-compliant installations.

    !
    Selecting by Zone Only

    Choosing equipment based only on Zone 1 or Zone 2 without checking the complete marking, gas or dust group and temperature requirements.

    !
    Confusing Protection Concepts

    Assuming Ex db, Ex eb and Ex p are interchangeable simply because products may be intended for the same hazardous area.

    !
    Ignoring Certificate Conditions

    Approving a product without checking special conditions of use, certified accessories, ambient limits or model variations.

    !
    Overlooking Installation Components

    Using unsuitable cable glands, stopping plugs, adapters or connection arrangements that may compromise the certified installation.

    FIELD ENGINEERING & INSTALLATION

    Ex Equipment Installation & Cable Entry Guide

    Practical guidance for selecting cable glands, managing cable entries and installing explosion-protected electrical equipment in hazardous areas.

    INSTALLATION FUNDAMENTALS

    Correct Equipment Requires Correct Installation

    Even correctly selected explosion-protected equipment can be compromised by unsuitable cable glands, incorrect adapters, improper cable termination or poor installation practices. Every connection must be compatible with the equipment design and its certified requirements.

    Ex INSTALLATION
    01 / CABLE GLAND SELECTION

    How to Select the Correct Ex Cable Gland

    Cable gland selection depends on more than the cable diameter. The enclosure protection concept, cable construction, installation environment and entry requirements must all be considered.

    01
    Identify the Equipment Protection

    Check the equipment marking and manufacturer's installation instructions to establish the required gland protection and permitted entry arrangement.

    02
    Identify Cable Construction

    Determine whether the cable is armoured or unarmoured, its insulation and sheath materials, and its construction and dimensions.

    03
    Confirm Cable Dimensions

    Check the overall cable diameter and, where applicable, the inner bedding diameter and armour dimensions against the gland manufacturer's selection range.

    04
    Confirm Entry Thread

    Verify the enclosure entry type, thread form, size and engagement requirements. Do not assume that metric and NPT threads are interchangeable.

    05
    Check Environmental Conditions

    Consider ambient temperature, ingress protection, corrosion, UV exposure, chemical exposure and installation location.

    06
    Verify the Gland Documentation

    Check the gland's certification, permitted cable types, temperature limits, installation instructions and any specific conditions of use.

    !

    Important Selection Principle

    A cable gland should not be selected based only on its thread size or cable diameter. Its suitability must be established for the complete installation arrangement.

    Protection Cable Type Thread Environment
    02 / CABLE CONSTRUCTION

    Armoured vs Unarmoured Cable Glands

    The cable construction determines the gland arrangement and the method used to secure the cable and maintain the required electrical and environmental protection.

    A
    ARMOURED CABLE

    Double Compression Cable Gland

    OUTER SHEATH ARMOUR INNER SHEATH CONDUCTORS

    Double compression glands are commonly used with armoured cables where the design provides sealing at the cable outer sheath and inner bedding, together with appropriate armour clamping.

    • Suitable for specified armoured cable constructions.
    • Provides mechanical retention and armour clamping.
    • Maintains the required sealing arrangement when correctly installed.
    • Supports the required electrical continuity and earthing arrangement where designed for that purpose.
    U
    UNARMOURED CABLE

    Single Compression Cable Gland

    OUTER SHEATH INNER INSULATION CONDUCTORS

    Single compression glands are commonly used with specified unarmoured cables, providing cable sealing and retention according to the gland design.

    • Suitable for the specified unarmoured cable type.
    • Provides sealing at the cable sheath.
    • Provides mechanical retention within the rated cable range.
    • May require additional consideration for cable protection and support.
    Note:

    Single and double compression describe gland construction and sealing arrangements. They do not, by themselves, establish suitability for a particular Ex protection concept or hazardous area.

    03 / BARRIER GLANDS

    When Should Barrier Cable Glands Be Considered?

    Barrier glands use a compound barrier system to seal around individual cable conductors and provide a defined sealing arrangement.

    GLAND BODY
    SEALING COMPOUND
    CABLE CONDUCTORS

    Compound Barrier Sealing

    The compound fills the spaces around the individual conductors within the specified gland design, creating a barrier against the passage of gases through the cable construction.

    01

    Check whether the equipment protection and installation requirements call for a barrier gland.

    02

    Consider cable construction, including fillers, bedding, conductor insulation and cable geometry.

    03

    Check the applicable installation standard, certificate conditions and manufacturer's instructions.

    04

    Follow the compound preparation, filling, curing and installation procedures specified by the gland manufacturer.

    !

    Do not assume that every Ex d installation requires a barrier gland. The requirement depends on the applicable installation standard, cable construction, installation conditions and the equipment or gland certification requirements.

    04 / CABLE ENTRY THREADS

    Understanding Cable Entry Thread Types

    Correct thread identification is essential to ensure mechanical compatibility and the required entry sealing arrangement.

    M

    Metric Threads

    M20 / M25 / M32

    Metric parallel threads are widely used in industrial electrical equipment and Ex enclosures.

    Example: M20 × 1.5
    NPT

    NPT Threads

    1/2" / 3/4" / 1"

    NPT is a tapered pipe thread system commonly encountered in equipment and installations following relevant US thread specifications.

    Example: 1/2" NPT
    G

    BSPP Threads

    G 1/2 / G 3/4

    BSPP is a parallel pipe thread system. The sealing arrangement must be appropriate for the specific connection design.

    Example: G 1/2
    i
    Important: Similar dimensions do not mean compatible threads.

    Metric, NPT and BSP thread systems have different profiles and specifications. Verify the exact thread type, pitch or taper, entry depth and permitted sealing method before installation.

    05 / CABLE ENTRY ACCESSORIES

    Adaptors, Reducers & Stopping Plugs

    Accessories used at Ex equipment cable entries must be appropriate for the enclosure, thread arrangement and intended protection requirements.

    A

    Thread Adaptors

    Used to connect different compatible thread sizes or types where an approved and suitable arrangement is permitted.

    Example: M25 to 3/4" NPT
    R

    Thread Reducers

    Used when a smaller cable entry is required, subject to the permitted enclosure entry and accessory configuration.

    Example: M32 to M25
    P

    Stopping Plugs

    Used to close unused cable entries. The plug must be suitable for the equipment protection and installation requirements.

    Example: M20 Ex stopping plug
    W

    Washers & Sealing Accessories

    Used where the equipment and accessory design specifies additional sealing or interface protection.

    Example: Certified sealing washer
    Installation rule:

    Never use an ordinary industrial plug, improvised thread converter or unsuitable washer to close or adapt an Ex equipment entry. Check the permitted accessories, thread engagement and installation instructions.

    06 / ELECTRICAL CONNECTIONS

    Earthing & Bonding in Ex Installations

    Proper earthing and bonding are essential for electrical safety and for maintaining the intended installation arrangement.

    01

    Protective Earthing

    Connect the equipment protective earthing terminal according to the equipment design and applicable installation requirements.

    02

    Internal & External Earth Terminals

    Use the designated earth terminals and verify the required conductor connection and mechanical security.

    03

    Armour Continuity

    Ensure the cable armour termination and bonding arrangement are suitable for the cable gland and installation design.

    04

    Equipotential Bonding

    Maintain the required bonding between conductive parts and the installation earthing system as specified by the project design.

    Cable armour should not automatically be assumed to replace the protective earth conductor. Its use as part of the protective earthing arrangement must be justified by the applicable design and installation requirements.
    07 / INSTALLATION QUALITY

    Common Installation Mistakes to Avoid

    Typical cable entry and installation problems that can compromise the intended equipment protection and electrical safety.

    !
    Using an Incorrect Gland Size

    A gland outside its specified cable diameter range may not provide the intended sealing or mechanical retention.

    !
    Mixing Thread Types

    Installing incompatible metric, NPT or BSP threads can cause poor engagement and an unsuitable entry arrangement.

    !
    Incorrect Armour Termination

    Improper armour clamping can affect mechanical retention and the intended electrical bonding arrangement.

    !
    Leaving Unused Entries Open

    Unused entries must be closed using suitable stopping plugs with the required protection and thread compatibility.

    !
    Unapproved Adaptors or Accessories

    Using unsuitable accessories can affect the enclosure entry arrangement and may invalidate the intended certified configuration.

    !
    Ignoring Manufacturer Instructions

    Incorrect assembly, sealing or tightening can compromise the intended gland performance.

    ASSET INTEGRITY & FIELD ENGINEERING

    Inspection & Maintenance of Ex Equipment

    Understand the inspection process, maintenance practices and common deterioration factors affecting electrical equipment installed in hazardous areas.

    OPERATIONAL SAFETY

    Maintaining Ex Equipment Throughout Its Service Life

    Explosion-protected equipment must remain in a condition that preserves its intended safety characteristics throughout operation. Regular inspection, appropriate maintenance and proper documentation help identify deterioration before it compromises the installation.

    Ex INSPECTION
    01 / INSPECTION TYPES

    Understanding the Different Types of Ex Inspection

    Inspection activities are selected according to the equipment, installation conditions, operating environment and applicable inspection procedures.

    01
    INITIAL

    Initial Inspection

    Performed before equipment or an installation is placed into service, to confirm that the installation has been carried out correctly.

    • Equipment identification and condition.
    • Correct installation and mounting.
    • Cable entries and accessories.
    • Earthing and bonding arrangements.
    • Compliance with installation documentation.
    02
    PERIODIC

    Periodic Inspection

    Scheduled inspection activities carried out during operation to identify deterioration, damage or changes affecting equipment safety.

    • Enclosure and external condition.
    • Corrosion and mechanical damage.
    • Gland and entry condition.
    • Earth connections and bonding.
    • Evidence of unauthorized modifications.
    03
    SAMPLE-BASED

    Sample Inspection

    Inspection of a selected proportion of equipment within an installation to assess its general condition and identify potential recurring issues.

    • Selection based on risk and inspection planning.
    • Review of representative equipment.
    • Identification of repeated defects.
    • Recommendations for further inspection.
    04
    TARGETED

    Special Inspection

    Additional inspection activities performed when specific conditions, incidents or identified risks require more detailed investigation.

    • After equipment damage or abnormal events.
    • Following modifications or repairs.
    • When repeated defects are identified.
    • When required by risk assessment or project procedures.
    Inspection planning:

    Inspection frequency and scope should be established through a documented inspection programme, considering the applicable standards, equipment criticality, environmental conditions and operating history.

    02 / INSPECTION GRADES

    Visual, Close & Detailed Inspection

    Inspection grades describe different levels of examination. The required grade determines how closely the equipment and installation details are assessed.

    V
    LEVEL 01

    Visual Inspection

    Identifies visible defects without requiring access equipment or tools, where the relevant inspection points are visible.

    • Visible physical damage.
    • Missing or loose components.
    • External corrosion.
    • Obvious cable entry defects.
    • Signs of unauthorized changes.
    C
    LEVEL 02

    Close Inspection

    Includes visual inspection and identifies defects that may only be detected using access equipment or closer examination.

    • Accessible mechanical condition.
    • Gland and cable entry condition.
    • Signs of deterioration around joints.
    • Condition of external connections.
    • Inspection of areas not easily visible from a distance.
    D
    LEVEL 03

    Detailed Inspection

    Includes the checks of close inspection and identifies defects requiring access to the inside of equipment or additional procedures.

    • Internal equipment condition where permitted.
    • Internal wiring and connections.
    • Internal signs of overheating or damage.
    • Inspection of accessible internal components.
    • Additional checks specified by the equipment documentation.
    Important distinction

    Visual, close and detailed inspections are different inspection grades, not automatic stages that every item must pass through in sequence. The appropriate grade is determined by the inspection programme and applicable requirements.

    03 / FIELD INSPECTION

    What Should Be Checked During an Ex Inspection?

    The following checklist covers common inspection points. The exact scope depends on the equipment type, protection concept and applicable inspection procedure.

    01

    Equipment Enclosure

    • Cracks, deformation or physical damage.
    • Corrosion and deterioration.
    • Missing or damaged fasteners.
    • Condition of covers and access points.
    02

    Cable Entries & Glands

    • Correct gland and entry arrangement.
    • Visible damage or corrosion.
    • Loose or improperly secured glands.
    • Unused entries properly closed.
    03

    Electrical Connections

    • External connection condition.
    • Signs of overheating or discoloration.
    • Damaged cable insulation.
    • Loose or deteriorated connections.
    04

    Earthing & Bonding

    • Earth terminal condition.
    • Mechanical security of connections.
    • Visible corrosion or deterioration.
    • Bonding arrangement integrity.
    05

    Environmental Condition

    • Water ingress and moisture.
    • Dust accumulation.
    • Chemical or corrosive exposure.
    • External temperature and UV effects.
    06

    Equipment Operation

    • Abnormal noise or vibration.
    • Unusual temperature rise.
    • Evidence of malfunction.
    • Unexpected operating conditions.
    04 / MAINTENANCE PRACTICES

    Maintaining Ex Equipment Correctly

    Maintenance activities must preserve the equipment's intended construction and operating characteristics. Work should be carried out by competent personnel following the manufacturer's instructions and applicable procedures.

    01

    Cleaning & Housekeeping

    Remove dust, dirt and other deposits using methods appropriate to the equipment and operating environment.

    Avoid methods or cleaning materials that may damage enclosure surfaces, seals or protective coatings.
    02

    Mechanical Condition

    Check enclosure integrity, covers, fasteners, mounting arrangements and other mechanical components.

    Replace damaged parts only with components permitted by the equipment manufacturer and applicable documentation.
    03

    Electrical Connections

    Inspect connection points and address deterioration, overheating or damage using approved maintenance procedures.

    Never carry out electrical work on energized equipment unless specifically permitted by the applicable safety procedures.
    04

    Seals & Gaskets

    Inspect sealing components where applicable and check for deterioration, damage or incorrect installation.

    Use only suitable replacement materials and components specified for the equipment.
    05

    Corrosion Protection

    Monitor corrosion, protective coatings and environmental damage affecting equipment enclosures and accessories.

    Repairs must not alter critical equipment surfaces or protection features.
    06

    Replacement Components

    Verify replacement parts and accessories are appropriate for the exact equipment model and installation arrangement.

    Do not substitute ordinary industrial components for specified Ex components.
    05 / EQUIPMENT DETERIORATION

    Common Factors Affecting Ex Equipment

    Operating conditions can gradually affect equipment integrity. Understanding these factors helps establish appropriate inspection and maintenance priorities.

    01

    Corrosion

    Exposure to moisture, chemicals, salt or aggressive industrial atmospheres can damage enclosure surfaces and mechanical components.

    02

    Vibration

    Continuous vibration can affect fasteners, cable connections, mounting points and electrical components.

    03

    Temperature Exposure

    High ambient temperatures and thermal cycling can accelerate material ageing and affect seals and electrical components.

    04

    Moisture & Water Ingress

    Water ingress can lead to corrosion, insulation deterioration and damage to internal electrical components.

    05

    Mechanical Impact

    Accidental impacts and physical damage can compromise enclosure integrity and equipment construction.

    06

    Unauthorized Modifications

    Uncontrolled drilling, machining, component substitution or modifications can compromise the original equipment design.

    06 / DEFECT MANAGEMENT

    Identifying & Managing Inspection Findings

    Inspection findings should be documented, assessed and assigned appropriate corrective actions according to the site's safety procedures and risk assessment.

    LOWER PRIORITY

    Minor Findings

    Issues that require attention but do not necessarily indicate an immediate loss of the required protection, subject to competent assessment.

    • Minor external deterioration.
    • Surface coating damage.
    • Housekeeping observations.
    Action: Record and schedule appropriate corrective work.
    REQUIRES ATTENTION

    Significant Findings

    Conditions that may affect equipment integrity or require further investigation and corrective maintenance.

    • Damaged cable entries.
    • Loose mechanical components.
    • Signs of moisture ingress.
    Action: Assess promptly and implement corrective measures.
    CRITICAL FINDINGS

    Potentially Unsafe Conditions

    Conditions that may compromise the required explosion protection or electrical safety and require immediate risk-based action.

    • Severely damaged enclosure.
    • Compromised protection-critical components.
    • Evidence of unsafe unauthorized modification.
    Action: Escalate immediately and apply site safety procedures, including isolation where required.
    Defect classification is site-specific.

    The examples above are illustrative, not universal defect grades. The responsible competent person must determine the actual risk, urgency and appropriate response.

    07 / PRACTICAL FIELD TOOL

    Ex Equipment Inspection Checklist

    Use this interactive checklist as a basic reference when reviewing the visible condition of equipment during an inspection.

    Field Inspection Review 0 of 10 items reviewed
    0%
    08 / INSPECTION DOCUMENTATION

    Why Inspection Records Matter

    Documenting inspection findings provides traceability and supports maintenance planning, corrective actions and future inspection activities.

    01

    Equipment Identification

    Equipment tag, location, manufacturer and relevant asset reference.

    02

    Inspection Details

    Inspection date, inspection type, grade and responsible personnel.

    03

    Findings & Evidence

    Observed defects, inspection observations and supporting photographs where appropriate.

    04

    Corrective Actions

    Recommended work, responsible party, action priority and completion status.

    05

    Follow-up Inspection

    Verification of corrective work and records of subsequent inspection activities.

    06

    Maintenance History

    Relevant maintenance interventions, replacement parts and equipment condition history.

    TECHNICAL REFERENCE

    Technical Glossary & FAQ

    A practical reference to commonly used hazardous-area and explosion-protection terminology, along with answers to frequently asked technical questions.

    Search by technical term, abbreviation, or keyword.

    REFERENCE LIBRARY

    Technical Glossary

    Key terms used in hazardous-area engineering and Ex equipment applications.

    14 TERMS
    H AREA & ENVIRONMENT

    Hazardous Area

    An area in which an explosive atmosphere is present, or may be expected to be present, in quantities requiring special precautions for the construction, installation and use of electrical equipment.

    E AREA & ENVIRONMENT

    Explosive Atmosphere

    A mixture of flammable substances in the form of gas, vapour, mist or dust with air, under atmospheric conditions, in which combustion can spread after ignition.

    Z AREA CLASSIFICATION

    Zone

    A classification of a hazardous area based on the frequency and duration of the occurrence of an explosive atmosphere. Zones are used to support equipment selection and installation decisions.

    E EQUIPMENT

    Equipment Protection Level (EPL)

    A designation indicating the level of protection assigned to equipment according to its potential to become an ignition source in an explosive atmosphere.

    C CABLE ENTRY

    Cable Gland

    A device fitted to an electrical enclosure to provide cable entry, mechanical retention and, where required, environmental sealing and other protection functions.

    B CABLE ENTRY

    Barrier Gland

    A cable gland incorporating a compound barrier system designed to seal around individual insulated conductors, where required by the equipment design and applicable installation conditions.

    S CABLE ENTRY

    Stopping Plug

    A component used to close an unused cable or conduit entry in an electrical enclosure. It must be suitable for the enclosure's protection concept and installation requirements.

    A CABLES

    Armoured Cable

    An electrical cable incorporating a metallic armour layer, commonly used to provide additional mechanical protection. The armour arrangement must be considered when selecting the cable entry system.

    U CABLES

    Unarmoured Cable

    An electrical cable without a metallic armour layer. Cable retention, sealing and environmental protection must be addressed through a suitable cable gland.

    I ENCLOSURE

    Ingress Protection (IP)

    A rating that describes the degree of protection provided by an enclosure against access to hazardous parts and the ingress of solid foreign objects and water, according to IEC 60529.

    E ELECTRICAL SAFETY

    Earthing & Bonding

    Earthing connects specified conductive parts to the earth. Bonding electrically connects conductive parts to maintain equipotential conditions and support electrical safety.

    A TEMPERATURE

    Ambient Temperature

    The temperature of the surrounding environment in which equipment operates. The permitted ambient temperature range must be considered when selecting and installing equipment.

    M TEMPERATURE

    Maximum Surface Temperature

    The highest temperature that a specified equipment surface can reach under the defined operating and fault conditions considered by its design and assessment.

    F ENCLOSURE DESIGN

    Flamepath

    A specially designed joint or passage between mating surfaces of a flameproof enclosure, intended to allow hot gases to cool before they reach the surrounding explosive atmosphere.

    No matching technical terms found. Try another keyword.
    COMMON QUESTIONS

    Frequently Asked Questions

    Practical answers to common questions about Ex equipment installation, inspection and maintenance.

    8 QUESTIONS
    01 How often should Ex equipment be inspected?

    There is no single inspection interval suitable for every installation. Inspection frequency should be established based on the installation conditions, equipment condition, environmental influences, operating experience and the applicable inspection requirements.

    The inspection programme should follow the principles and requirements of IEC 60079-17, together with the site's maintenance and risk-management procedures.

    02 Who is qualified to inspect Ex equipment?

    Ex equipment should be inspected by personnel with appropriate competence, training and experience in hazardous-area installations. They should understand the relevant protection concepts, equipment documentation, inspection requirements and applicable standards.

    The required level of competence depends on the inspection task and the complexity of the installation.

    03 Can an Ex enclosure be drilled or modified on site?

    Ex enclosures should not be drilled, machined or modified without an appropriate technical assessment and authorization.

    Any modification may affect the equipment's protection characteristics, enclosure integrity or certified design. Modifications must follow the manufacturer's instructions and applicable requirements.

    04 Can damaged Ex equipment remain in service?

    Equipment with damage that may compromise its protection should not be assumed safe for continued operation.

    It should be assessed by competent personnel. Where the condition presents a safety concern, the equipment should be isolated in accordance with the site's safety procedures until the issue has been resolved.

    05 Can standard accessories be used with Ex cable entries?

    Not automatically. Cable glands, adaptors, reducers, stopping plugs and other entry accessories must be suitable for the equipment's protection concept, thread type, cable construction and installation conditions.

    Their use must also be consistent with the equipment manufacturer's documentation and applicable installation requirements.

    06 What records should be maintained for Ex equipment inspections?

    Inspection records should provide sufficient information to demonstrate the condition and maintenance history of the installation.

    • Equipment identification and location.
    • Inspection date and inspection type.
    • Inspection findings and identified defects.
    • Corrective actions and responsible personnel.
    • Repair or replacement details, where applicable.
    • Follow-up inspection and closure status.
    07 Does an IP rating alone confirm that equipment is suitable for hazardous areas?

    No. An IP rating describes protection against access to hazardous parts and the ingress of solids and water. It does not, by itself, establish explosion protection suitability.

    Equipment selection must consider the hazardous-area requirements, protection concept, equipment marking, operating conditions and relevant technical documentation.

    08 Can the same cable gland be used with all cable types?

    No. Cable glands are designed for specific cable constructions and dimensional ranges. Selection should consider whether the cable is armoured or unarmoured, its outer diameter, bedding and inner sheath arrangement, armour type and installation conditions.

    Always check the gland manufacturer's technical documentation before selecting a cable entry solution.

    No matching questions found. Try another keyword.
    NEED TECHNICAL ASSISTANCE?

    Looking for the Right Ex Equipment for Your Application?

    Our team can support your equipment selection and technical requirements for hazardous-area applications.

    i

    Technical Note: The information provided in this section is intended as a general technical reference. It does not replace applicable international standards, manufacturer instructions, equipment documentation, project specifications or assessment by competent personnel. Equipment selection and installation must be evaluated according to the actual hazardous-area conditions and applicable requirements.